OPC-UA Client
Parameters
| Parameter | Datatype | Default Value | Description |
|---|---|---|---|
| URL | string | OPC-UA server endpoint URL(s), comma-separated for round-robin failover | |
| DEFAULT_NAMESPACE | integer | 1 | Default namespace |
| USERNAME | string | Username (leave empty for anonymous access) | |
| PASSWORD | string | Password | |
| TIMEOUT | float | 5 | Network timeout [s] |
| SCAN_PERIOD | float | 1 | Poll period [s] |
| RECONNECT_INTERVAL | float | 1 | Reconnection interval after connection loss [s] |
| MAX_ITEMS_PER_SUB | integer | 5000 | Maximum monitored items per OPC-UA subscription |
| DEBUG | enum | 0 | Enable debugging |
Measurements
This stack supports measurements.
Measurement address
Type: regex
Description:
[uatype@]<nodeId>
uatype (optional): boolean | sbyte | byte | int16 | uint16 | int32 | uint32 | int64 | uint64 | float | double | string
If omitted, the CO's configured raw datatype is used.
nodeId: OPC-UA node identifier string
ns=<index>;i=<number> - numeric node id
ns=<index>;s=<name> - string node id
ns=<index>;<name> - string node id
i=<number> - numeric node id in default namespace
s=<name> - string node id in default namespace
<name> - string node id in default namespace
Examples:
ns=2;i=1001
ns=2;s=Sensors.Temperature
float@ns=2;s=Room.Humidity
int32@i=12345
Room.Humidity
Commands
This stack supports commands.
Command address
Type: regex
Description:
[uatype@]<nodeId>
uatype (optional): boolean | sbyte | byte | int16 | uint16 | int32 | uint32 | int64 | uint64 | float | double | string
If omitted, the CO's configured raw datatype is used.
nodeId: OPC-UA node identifier string
ns=<index>;i=<number> - numeric node id
ns=<index>;s=<name> - string node id
ns=<index>;<name> - string node id
i=<number> - numeric node id in default namespace
s=<name> - string node id in default namespace
<name> - string node id in default namespace
Examples:
ns=2;i=2001
ns=2;s=Actuators.Setpoint
double@ns=2;s=Controller.Setpoint
Controller.Setpoint